Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
57.60 - 320A
Adjustment range short-term delayed short-circuit release
192.0 - 3200A
Rated permanent current Iu
400A
Integrated earth fault protection
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
480.0 - 3680.0A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Front side
With switched-off indicator
No
Number of poles
4
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Motor drive integrated
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive optional
Yes
From same serie
1SDA081056R1 | T5L 400 EKIP E-LSIG IN=320A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Overload release current setting
57.60 .. 320A
Adjustment range short-term delayed short-circuit release
192.0 .. 3200A
Rated permanent current Iu
400A
Integrated earth fault protection
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
480.0 .. 3680.0A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Front side
With switched-off indicator
Number of poles
4
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Motor drive integrated
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive optional
From same serie