Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Integrated earth fault protection
No
Rated permanent current Iu
630A
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
378.0 - 5985A
Number of poles
4
With switched-off indicator
No
Motor drive integrated
No
Overload release current setting
113.40 - 630A
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Number of auxiliary contacts as change-over contact
0
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
945.0 - 5985A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
From same serie
1SDA081070R1 | T5H 630 EKIP E-LSIG IN=630A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Integrated earth fault protection
Rated permanent current Iu
630A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
378.0 .. 5985A
Number of poles
4
With switched-off indicator
Motor drive integrated
Overload release current setting
113.40 .. 630A
Position of connection for main current circuit
Front side
Complete device with protection unit
Degree of protection (IP)
IP20
Number of auxiliary contacts as change-over contact
0
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Adjustment range undelayed short-circuit release
945.0 .. 5985A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique