Technical specifications

Mounting methodDIN rail (top hat rail) 35 mm
Construction size4 modular spacing
ExhaustingNo
Voltage protection level L-N1.3kV
Signalling at the deviceOptic
Follow current extinguishing capability-kA
Test classType 1 + 2
System configuration DCNo
Max. conductor cross section solid (solid, stranded)35mm²
Nominal voltage DC-V
Integrated backup fuseNo
Voltage protection level N-PE1.3kV
System configuration ITNo
Voltage protection level (DC+ - DC-)-kV
Voltage protection level (DC+/DC- - PE)-kV
System configuration TNNo
Energy-coordinated protection effect with regard to the terminal equipmentNo
Max. continuous voltage DC-V
Max. PV-voltage-V
Max. conductor cross section flexible (fine-strand)25mm²
Specific energy (W/R)-kJ/Ohm
System configuration TTYes
System configuration TN-SYes
System configuration TN-CNo
Voltage protection level L-PE1.4kV
System configuration otherNo
System configuration TN-C-SNo
Remote signallingYes
Max. continuous voltage AC275V
Lightning impulse current (10/350 µs)12.5kA
Number of poles4
Voltage protection level0.8kV
Nominal voltage AC230V
Degree of protection (IP)IP20

Recommended products


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB815710R0700 | OVR T1-T2 3N 12.5-275s P TS QS

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Mounting method

DIN rail (top hat rail) 35 mm

Construction size

4 modular spacing

Exhausting

Voltage protection level L-N

1.3kV

Signalling at the device

Optic

Follow current extinguishing capability

-kA

Test class

Type 1 + 2

System configuration DC

Max. conductor cross section solid (solid, stranded)

35mm²

Nominal voltage DC

-V

Integrated backup fuse

Voltage protection level N-PE

1.3kV

System configuration IT

Voltage protection level (DC+ - DC-)

-kV

Voltage protection level (DC+/DC- - PE)

-kV

System configuration TN

Energy-coordinated protection effect with regard to the terminal equipment

Max. continuous voltage DC

-V

Max. PV-voltage

-V

Max. conductor cross section flexible (fine-strand)

25mm²

Specific energy (W/R)

-kJ/Ohm

System configuration TT

System configuration TN-S

System configuration TN-C

Voltage protection level L-PE

1.4kV

System configuration other

System configuration TN-C-S

Remote signalling

Max. continuous voltage AC

275V

Lightning impulse current (10/350 µs)

12.5kA

Number of poles

4

Voltage protection level

0.8kV

Nominal voltage AC

230V

Degree of protection (IP)

IP20