Technical specifications

Construction size2 modular spacing
Lightning impulse current (10/350 µs)12.5kA
Mounting methodDIN rail (top hat rail) 35 mm
Number of poles1
Voltage protection level0.5kV
Voltage protection level N-PE1.3kV
System configuration TNYes
System configuration ITNo
Nominal voltage DC560V
Integrated backup fuseNo
Nominal voltage AC400V
Max. conductor cross section solid (solid, stranded)35mm²
Energy-coordinated protection effect with regard to the terminal equipmentNo
Remote signallingYes
Voltage protection level L-N1.3kV
Degree of protection (IP)IP20
Max. continuous voltage AC440V
System configuration DCNo
Voltage protection level (DC+ - DC-)-kV
Max. PV-voltage-V
Signalling at the deviceOptic
Specific energy (W/R)-kJ/Ohm
ExhaustingNo
Max. continuous voltage DC560V
Max. conductor cross section flexible (fine-strand)25mm²
Test classType 1 + 2
System configuration TN-CYes
Voltage protection level (DC+/DC- - PE)-kV
Follow current extinguishing capability-kA
System configuration otherNo
System configuration TTYes
Voltage protection level L-PE1.9kV
Overcurrent protected voltage tappingNo
Voltage switching spark gap technologyNo
Max. overcurrent protection device, series connection (fuse)-A
System configuration TN-C-SNo
Max. overcurrent protection device, parallel connection (fuse)-A
System configuration TN-SYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB815710R2900 | OVR T1-T2 12.5-440s P TS QS

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Construction size

2 modular spacing

Lightning impulse current (10/350 µs)

12.5kA

Mounting method

DIN rail (top hat rail) 35 mm

Number of poles

1

Voltage protection level

0.5kV

Voltage protection level N-PE

1.3kV

System configuration TN

System configuration IT

Nominal voltage DC

560V

Integrated backup fuse

Nominal voltage AC

400V

Max. conductor cross section solid (solid, stranded)

35mm²

Energy-coordinated protection effect with regard to the terminal equipment

Remote signalling

Voltage protection level L-N

1.3kV

Degree of protection (IP)

IP20

Max. continuous voltage AC

440V

System configuration DC

Voltage protection level (DC+ - DC-)

-kV

Max. PV-voltage

-V

Signalling at the device

Optic

Specific energy (W/R)

-kJ/Ohm

Exhausting

Max. continuous voltage DC

560V

Max. conductor cross section flexible (fine-strand)

25mm²

Test class

Type 1 + 2

System configuration TN-C

Voltage protection level (DC+/DC- - PE)

-kV

Follow current extinguishing capability

-kA

System configuration other

System configuration TT

Voltage protection level L-PE

1.9kV

Overcurrent protected voltage tapping

Voltage switching spark gap technology

Max. overcurrent protection device, series connection (fuse)

-A

System configuration TN-C-S

Max. overcurrent protection device, parallel connection (fuse)

-A