  • •ODVODNIK PRENAPONA,TIP T1+T2, 440V, SA SIGURNOSOM
  • •Earthing, lightning and surge protection
  • •Combined arrester for power supply systems
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

Construction size2 modular spacing
Mounting methodDIN rail (top hat rail) 35 mm
Voltage protection level N-PE1.3kV
System configuration TNYes
System configuration ITNo
Nominal voltage DC560V
Integrated backup fuseNo
Max. conductor cross section solid (solid, stranded)35mm²
Energy-coordinated protection effect with regard to the terminal equipmentNo
Remote signallingYes
Voltage protection level L-N1.3kV
Max. continuous voltage AC440V
System configuration DCNo
Voltage protection level (DC+ - DC-)-kV
Max. PV-voltage-V
Signalling at the deviceOptic
Specific energy (W/R)-kJ/Ohm
ExhaustingNo
Max. continuous voltage DC560V
Max. conductor cross section flexible (fine-strand)25mm²
Test classType 1 + 2
System configuration TN-CYes
Voltage protection level (DC+/DC- - PE)-kV
Follow current extinguishing capability-kA
System configuration otherNo
System configuration TTYes
Voltage protection level L-PE1.9kV
Overcurrent protected voltage tappingNo
Voltage switching spark gap technologyNo
Max. overcurrent protection device, series connection (fuse)-A
System configuration TN-C-SNo
Max. overcurrent protection device, parallel connection (fuse)-A
System configuration TN-SYes
Lightning impulse current (10/350 µs)12.5kA
Number of poles1
Voltage protection level0.5kV
Nominal voltage AC400V
Degree of protection (IP)IP20