Details
- •Earthing, lightning and surge protection
- •Surge protection device for power supply systems
- •1 KOM
- •SCHNEIDER
Technical specifications
Max. continuous voltage AC460V
Voltage protection level1.6kV
Mounting methodDIN rail (top hat rail) 35 mm
Number of conductors (without earthing)3
With remote signalling contactYes
Construction size6 modular spacing
Nominal voltage DC-V
Signalling at the deviceOptic
Voltage protection level L-N1.4kV
Max. conductor cross section solid (solid, stranded)25mm²
Voltage protection level N-PE-kV
Max. conductor cross section flexible (fine-strand)16mm²
System configuration ITYes
System configuration otherNo
System configuration DCNo
Category type 2Yes
Integrated backup fuseNo
System configuration TNNo
System configuration TTNo
Max. overcurrent protection device, parallel connection (fuse)25A
System configuration TN-CNo
Max. continuous voltage DC-V
Max. discharge surge current (8/20)8kA
Integrated short-circuit protectionNo
Max. overcurrent protection device, series connection (fuse)80A
Max. PV-voltage-V
Short-circuit breaking capacity (Isccr)50kA
System configuration TN-SNo
System configuration TN-C-SNo
Leakage-current freeNo
Nominal discharge surge current (8/20)2.5kA
Nominal voltage AC400V
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user