Details

  • •U?inski prekida?, h250, 3P, 125A, 40kA, TM ( ter
  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •1 KOM
  • •HAGER

Technical specifications

Number of auxiliary contacts as normally closed contact0
With switched-off indicatorNo
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
With integrated under voltage releaseNo
Type of control elementToggle
Overload release current setting80 - 125A
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Degree of protection (IP)IP40
Power loss27.7W
Type of electrical connection of main circuitScrew connection
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release750 - 1625A
Adjustment range short-term delayed short-circuit release0 - 0A
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Rated permanent current Iu125A
Number of poles3
Rated voltage220 - 415V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz40kA

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user