Details

  • •U?inski prekida?, h1600, 4P, 1250A, 50kA, LSI
  • •Low-voltage industrial components
  • •Power circuit-breaker for trafo/generator/installation protection
  • •1 KOM
  • •HAGER

Technical specifications

With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP40
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Power loss187.5W
Overload release current setting500 - 1250A
With switched-off indicatorNo
Motor drive integratedNo
Type of electrical connection of main circuitScrew connection
Type of control elementToggle
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release0 - 0A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release7000 - 15000A
Complete device with protection unitYes
Motor drive optionalYes
Rated permanent current Iu1250A
Number of poles4
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user