Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • HAGER

Technical specifications

Rated current40A
Built-in depth70mm
Pollution degree2
Concurrently switching neutral conductorNo
Width in number of modular spacings2
Voltage typeAC
Frequency50 - 60Hz
Release characteristicB
Number of protected poles2
Degree of protection (IP)IP20
Rated voltage400V
Over voltage category3
Current limiting class3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Number of poles (total)2
Additional equipment possibleYes
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V15kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Suitable for flush-mounted installationYes
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V30kA

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NBN240

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • HAGER

Technical specifications

Rated current

40A

Built-in depth

70mm

Pollution degree

2

Concurrently switching neutral conductor

Width in number of modular spacings

2

Voltage type

AC

Frequency

50 .. 60Hz

Release characteristic

B

Number of protected poles

2

Degree of protection (IP)

IP20

Rated voltage

400V

Over voltage category

3

Current limiting class

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Number of poles (total)

2

Additional equipment possible

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

15kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Suitable for flush-mounted installation

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

30kA