Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • LEGRAND

Technical specifications

Degree of protection (IP)IP20
Over voltage category-
Frequency50 - 60Hz
Width in number of modular spacings3
Connectable conductor cross section solid-core1.5 - 50mm²
Suitable for flush-mounted installationYes
Rated insulation voltage Ui500V
Built-in depth47mm
Connectable conductor cross section multi-wired1.5 - 35mm²
Additional equipment possibleYes
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V-kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V100kA
Ambient temperature during operating-25 - 70°C
Concurrently switching neutral conductorNo
Number of protected poles2
Current limiting class-
Pollution degree3
Rated impulse withstand voltage Uimp6kV
Voltage typeAC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V50kA
Rated voltage400V
Rated current25A
Release characteristicD
Number of poles (total)2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V-kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user