  • Low-voltage industrial components
  • Motor protection circuit-breaker
  • 1 KOM
  • LEGRAND

Technical specifications

Height165mm
Depth171mm
Width70mm
With integrated under voltage releaseYes
With integrated auxiliary switchYes
Rated operating voltage220 - 690V
Rated operation power at AC-3, 230 V30kW
Type of electrical connection of main circuitFrame clamp
Switch off techniqueThermomagnetic
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release1300 - 1300A
Phase failure sensitiveNo
Degree of protection (IP)IP20
Type of control elementTurn button
With thermal protectionYes
Rated operation power at AC-3, 400 V45kW
Rated permanent current Iu100A
Number of poles3
Overload release current setting80 - 100A
Rated short-circuit breaking capacity lcu at 400 V, AC75kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

417379 | MPX 100H MOT Prek TM 80-100A

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Motor protection circuit-breaker
  • 1 KOM
  • LEGRAND

Technical specifications

Height

165mm

Depth

171mm

Width

70mm

With integrated under voltage release

With integrated auxiliary switch

Rated operating voltage

220 .. 690V

Rated operation power at AC-3, 230 V

30kW

Type of electrical connection of main circuit

Frame clamp

Switch off technique

Thermomagnetic

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

1300 .. 1300A

Phase failure sensitive

Degree of protection (IP)

IP20

Type of control element

Turn button

With thermal protection

Rated operation power at AC-3, 400 V

45kW

Rated permanent current Iu

100A

Number of poles

3

Overload release current setting

80 .. 100A

Rated short-circuit breaking capacity lcu at 400 V, AC

75kA