Technical specifications

Degree of protection (IP)IP30
Type of control elementToggle
Number of poles3
Number of auxiliary contacts as normally closed contact1
Number of auxiliary contacts as normally open contact-
Rated permanent current Iu80A
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Rated voltage220 - 690V
Type of electrical connection of main circuitScrew connection
Number of auxiliary contacts as change-over contact1
Motor drive integratedNo
Overload release current setting64 - 80A
Adjustment range undelayed short-circuit release800 - 800A
Suitable for DIN rail (top hat rail) mountingYes
With under voltage releaseYes
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz16kA
Adjustment range short-term delayed short-circuit release800 - 800A
Position of connection for main current circuitFront side
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalYes
Integrated earth fault protectionNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

420004 | DPX3 160-TM 3P 80A 16KA

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • LEGRAND

Technical specifications

Degree of protection (IP)

IP30

Type of control element

Toggle

Number of poles

3

Number of auxiliary contacts as normally closed contact

1

Number of auxiliary contacts as normally open contact

-

Rated permanent current Iu

80A

Motor drive optional

Device construction

Built-in device fixed built-in technique

Rated voltage

220 .. 690V

Type of electrical connection of main circuit

Screw connection

Number of auxiliary contacts as change-over contact

1

Motor drive integrated

Overload release current setting

64 .. 80A

Adjustment range undelayed short-circuit release

800 .. 800A

Suitable for DIN rail (top hat rail) mounting

With under voltage release

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

16kA

Adjustment range short-term delayed short-circuit release

800 .. 800A

Position of connection for main current circuit

Front side

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.