Technical specifications
Number of auxiliary contacts as normally open contact-
Number of auxiliary contacts as normally closed contact1
Overload release current setting200 - 250A
Number of auxiliary contacts as change-over contact1
Type of electrical connection of main circuitScrew connection
Degree of protection (IP)IP30
Position of connection for main current circuitFront side
Motor drive integratedNo
Type of control elementToggle
Adjustment range short-term delayed short-circuit release1250 - 2500A
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1250 - 2500A
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingYes
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalYes
With under voltage releaseYes
Rated permanent current Iu250A
Number of poles3
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA