Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration TNNo
System configuration TTNo
Voltage protection level L-PE2.8kV
Voltage protection level L-N1.5kV
Construction sizeOther
System configuration DCNo
System configuration TN-C-SNo
System configuration ITYes
Max. continuous voltage AC350V
Mounting methodDIN rail (top hat rail) 35 mm
Max. overcurrent protection device, parallel connection (fuse)315A
Voltage protection level N-PE1.5kV
Follow current extinguishing capability25kA
Voltage protection level2.8kV
Max. overcurrent protection device, series connection (fuse)125A
System configuration otherNo
System configuration TN-SNo
System configuration TN-CNo
Voltage switching spark gap technologyNo
Signalling at the deviceOptic
Max. conductor cross section flexible (fine-strand)35mm²
Remote signallingYes
Test classType 1
Integrated backup fuseYes
Degree of protection (IP)IP20
Max. conductor cross section solid (solid, stranded)35mm²

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1044386 | FLT-SEC-T1+T2-3IT-350/25-FM

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Combined arrester for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration TN

System configuration TT

Voltage protection level L-PE

2.8kV

Voltage protection level L-N

1.5kV

Construction size

Other

System configuration DC

System configuration TN-C-S

System configuration IT

Max. continuous voltage AC

350V

Mounting method

DIN rail (top hat rail) 35 mm

Max. overcurrent protection device, parallel connection (fuse)

315A

Voltage protection level N-PE

1.5kV

Follow current extinguishing capability

25kA

Voltage protection level

2.8kV

Max. overcurrent protection device, series connection (fuse)

125A

System configuration other

System configuration TN-S

System configuration TN-C

Voltage switching spark gap technology

Signalling at the device

Optic

Max. conductor cross section flexible (fine-strand)

35mm²

Remote signalling

Test class

Type 1

Integrated backup fuse

Degree of protection (IP)

IP20

Max. conductor cross section solid (solid, stranded)

35mm²

Related products

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.