System configuration DCNo
System configuration TNNo
System configuration ITNo
System configuration TN-CNo
System configuration TN-C-SNo
System configuration TTNo
Max. discharge surge current (8/20)40kA
System configuration otherNo
System configuration TN-SYes
Max. continuous voltage AC440V
Voltage protection level1.9kV
Max. overcurrent protection device, parallel connection (fuse)315A
Voltage protection level N-PE1.9kV
Max. overcurrent protection device, series connection (fuse)40A
Short-circuit breaking capacity (Isccr)50kA
Voltage protection level L-N4kV
Integrated backup fuseYes
Mounting methodDIN rail (top hat rail) 35 mm
With remote signalling contactYes
Max. conductor cross section flexible (fine-strand)16mm²
Max. conductor cross section solid (solid, stranded)2.5mm²
Signalling at the deviceOptic
Nominal discharge surge current (8/20)20kA
Degree of protection (IP)IP20