Technical specifications
Nominal discharge surge current (8/20)
20kA
System configuration IT
System configuration TN-S
Max. discharge surge current (8/20)
40kA
System configuration TN-C-S
Max. continuous voltage AC
350V
System configuration other
System configuration TN-C
System configuration TT
Voltage protection level N-PE
1.5kV
Max. overcurrent protection device, series connection (fuse)
40A
Integrated backup fuse
Voltage protection level
1.9kV
Voltage protection level L-N
1.5kV
Short-circuit breaking capacity (Isccr)
50kA
System configuration TN
System configuration DC
Max. overcurrent protection device, parallel connection (fuse)
315A
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
Other
With remote signalling contact
Leakage-current free
Max. conductor cross section flexible (fine-strand)
16mm²
Category type 2
Max. conductor cross section solid (solid, stranded)
2.5mm²
Degree of protection (IP)
IP20
Signalling at the device
Optic