System configuration ITNo
System configuration DCNo
System configuration TN-C-SNo
System configuration TNNo
System configuration TN-SNo
Max. discharge surge current (8/20)40kA
Voltage protection level L-N0.85kV
System configuration otherNo
System configuration TTNo
System configuration TN-CYes
Max. continuous voltage AC175V
Max. overcurrent protection device, parallel connection (fuse)315A
Max. overcurrent protection device, series connection (fuse)40A
Integrated backup fuseYes
Mounting methodDIN rail (top hat rail) 35 mm
Short-circuit breaking capacity (Isccr)50kA
Max. conductor cross section flexible (fine-strand)16mm²
With remote signalling contactYes
Signalling at the deviceOptic
Max. conductor cross section solid (solid, stranded)2.5mm²
Nominal discharge surge current (8/20)20kA
Degree of protection (IP)IP20