Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration ITNo
System configuration DCNo
Nominal discharge surge current (8/20)20kA
System configuration otherNo
System configuration TN-CYes
System configuration TN-C-SNo
System configuration TNNo
System configuration TN-SNo
System configuration TTNo
Max. discharge surge current (8/20)40kA
Voltage protection level L-N0.85kV
Max. continuous voltage AC175V
Leakage-current freeNo
Max. overcurrent protection device, parallel connection (fuse)315A
Max. overcurrent protection device, series connection (fuse)40A
Short-circuit breaking capacity (Isccr)50kA
Integrated backup fuseYes
Mounting methodDIN rail (top hat rail) 35 mm
Category type 2Yes
Degree of protection (IP)IP20
Max. conductor cross section flexible (fine-strand)16mm²
With remote signalling contactYes
Max. conductor cross section solid (solid, stranded)2.5mm²
Construction sizeOther
Signalling at the deviceOptic

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2905353 | VAL-SEC-T2-3C-175-FM

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration IT

System configuration DC

Nominal discharge surge current (8/20)

20kA

System configuration other

System configuration TN-C

System configuration TN-C-S

System configuration TN

System configuration TN-S

System configuration TT

Max. discharge surge current (8/20)

40kA

Voltage protection level L-N

0.85kV

Max. continuous voltage AC

175V

Leakage-current free

Max. overcurrent protection device, parallel connection (fuse)

315A

Max. overcurrent protection device, series connection (fuse)

40A

Short-circuit breaking capacity (Isccr)

50kA

Integrated backup fuse

Mounting method

DIN rail (top hat rail) 35 mm

Category type 2

Degree of protection (IP)

IP20

Max. conductor cross section flexible (fine-strand)

16mm²

With remote signalling contact

Max. conductor cross section solid (solid, stranded)

2.5mm²

Construction size

Other

Signalling at the device

Optic

Related products

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.