Details
- •Earthing, lightning and surge protection
- •Surge protection device for power supply systems
- •1 KOM
- •PHOENIX
Technical specifications
2906101 | BLT-T2-1S-320-UT

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- PHOENIX
Technical specifications
Nominal discharge surge current (8/20)
5kA
System configuration other
Voltage protection level L-N
1.3kV
System configuration TT
System configuration TN-S
Max. discharge surge current (8/20)
10kA
Max. overcurrent protection device, series connection (fuse)
16A
Voltage protection level
1.5kV
Voltage protection level N-PE
1.4kV
System configuration TN-C
System configuration TN-C-S
Max. continuous voltage AC
320V
Max. overcurrent protection device, parallel connection (fuse)
16A
System configuration TN
System configuration IT
Short-circuit breaking capacity (Isccr)
3kA
Integrated backup fuse
System configuration DC
Max. conductor cross section solid (solid, stranded)
0.2mm²
Signalling at the device
Optic
Degree of protection (IP)
IP20
Leakage-current free
Max. conductor cross section flexible (fine-strand)
2.5mm²
Category type 2