System configuration DCNo
System configuration TN-CNo
System configuration TNNo
System configuration TN-C-SNo
System configuration TTNo
System configuration otherNo
System configuration ITNo
Max. continuous voltage AC440V
Voltage protection level N-PE2.5kV
Voltage protection level L-N4.5kV
With remote signalling contactYes
Follow current extinguishing capability50kA
Max. conductor cross section solid (solid, stranded)35mm²
System configuration TN-SYes
Max. conductor cross section flexible (fine-strand)35mm²
Signalling at the deviceOptic
Integrated backup fuseYes
Degree of protection (IP)IP20
Suitable for outdoor useNo
Mounting methodDIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs)35kA