Details
- •Earthing, lightning and surge protection
- •Surge protection device for power supply systems
- •1 KOM
- •PHOENIX
Technical specifications
Related products
2910352 | VAL-US-120/40/2+1-FM

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- PHOENIX
Technical specifications
System configuration TN
System configuration TN-C
System configuration IT
System configuration TN-S
System configuration DC
System configuration TN-C-S
System configuration TT
Max. overcurrent protection device, series connection (fuse)
80A
Nominal discharge surge current (8/20)
20kA
Voltage protection level
1.6kV
Short-circuit breaking capacity (Isccr)
25kA
Voltage protection level L-N
0.9kV
Max. overcurrent protection device, parallel connection (fuse)
125A
System configuration other
Integrated backup fuse
Voltage protection level N-PE
1.5kV
Leakage-current free
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
Other
Degree of protection (IP)
IP20
Signalling at the device
Optic
Max. conductor cross section solid (solid, stranded)
1.5mm²
Max. conductor cross section flexible (fine-strand)
25mm²
With remote signalling contact
Category type 2