System configuration ITNo
System configuration TN-CYes
System configuration TNNo
Integrated backup fuseYes
System configuration TN-SNo
System configuration otherNo
System configuration TN-C-SNo
System configuration DCNo
Max. overcurrent protection device, series connection (fuse)80A
System configuration TTNo
Short-circuit breaking capacity (Isccr)25kA
Voltage protection level L-N0.9kV
Max. conductor cross section solid (solid, stranded)1.5mm²
Mounting methodDIN rail (top hat rail) 35 mm
Max. overcurrent protection device, parallel connection (fuse)125A
Max. conductor cross section flexible (fine-strand)25mm²
Signalling at the deviceOptic
With remote signalling contactYes
Nominal discharge surge current (8/20)20kA
Degree of protection (IP)IP20