System configuration DCNo
System configuration ITNo
System configuration TNNo
System configuration TN-SNo
System configuration TN-C-SNo
System configuration otherNo
System configuration TTNo
System configuration TN-CYes
Max. continuous voltage AC385V
Voltage protection level L-N1.8kV
Max. discharge surge current (8/20)40kA
Short-circuit breaking capacity (Isccr)25kA
Integrated backup fuseYes
Max. overcurrent protection device, parallel connection (fuse)125A
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section flexible (fine-strand)25mm²
With remote signalling contactYes
Max. conductor cross section solid (solid, stranded)1.5mm²
Signalling at the deviceOptic
Nominal discharge surge current (8/20)20kA
Degree of protection (IP)IP20