Technical specifications

System configuration DCNo
System configuration TTNo
System configuration TN-C-SNo
System configuration ITNo
System configuration TNNo
System configuration otherNo
System configuration TN-CYes
System configuration TN-SNo
Voltage protection level L-N1.35kV
Max. discharge surge current (8/20)40kA
Max. continuous voltage AC275V
Nominal discharge surge current (8/20)20kA
Max. overcurrent protection device, parallel connection (fuse)125A
Short-circuit breaking capacity (Isccr)25kA
Leakage-current freeNo
Construction sizeOther
Integrated backup fuseYes
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section solid (solid, stranded)1.5mm²
Max. conductor cross section flexible (fine-strand)25mm²
With remote signalling contactYes
Degree of protection (IP)IP20
Signalling at the deviceOptic
Category type 2Yes

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2910369 | VAL-US-240D/40/2+0-FM

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • PHOENIX

Technical specifications

System configuration DC

System configuration TT

System configuration TN-C-S

System configuration IT

System configuration TN

System configuration other

System configuration TN-C

System configuration TN-S

Voltage protection level L-N

1.35kV

Max. discharge surge current (8/20)

40kA

Max. continuous voltage AC

275V

Nominal discharge surge current (8/20)

20kA

Max. overcurrent protection device, parallel connection (fuse)

125A

Short-circuit breaking capacity (Isccr)

25kA

Leakage-current free

Construction size

Other

Integrated backup fuse

Mounting method

DIN rail (top hat rail) 35 mm

Max. conductor cross section solid (solid, stranded)

1.5mm²

Max. conductor cross section flexible (fine-strand)

25mm²

With remote signalling contact

Degree of protection (IP)

IP20

Signalling at the device

Optic

Category type 2

Related products