System configuration ITNo
System configuration TN-C-SNo
System configuration DCNo
Mounting methodDIN rail (top hat rail) 35 mm
Max. discharge surge current (8/20)40kA
System configuration otherNo
Voltage protection level N-PE1.5kV
Max. continuous voltage AC175V
Integrated backup fuseYes
System configuration TN-SYes
Short-circuit breaking capacity (Isccr)25kA
System configuration TN-CNo
System configuration TTNo
System configuration TNNo
Voltage protection level L-N0.9kV
Max. overcurrent protection device, parallel connection (fuse)125A
Max. conductor cross section solid (solid, stranded)1.5mm²
With remote signalling contactYes
Signalling at the deviceOptic
Max. conductor cross section flexible (fine-strand)25mm²
Nominal discharge surge current (8/20)20kA
Degree of protection (IP)IP20