System configuration TTNo
System configuration TNNo
System configuration DCNo
System configuration ITNo
System configuration TN-CYes
System configuration TN-C-SNo
Max. discharge surge current (8/20)30kA
System configuration TN-SNo
System configuration otherNo
Max. continuous voltage AC750V
Max. overcurrent protection device, parallel connection (fuse)100A
Integrated backup fuseYes
Short-circuit breaking capacity (Isccr)25kA
Voltage protection level L-N2.9kV
Mounting methodDIN rail (top hat rail) 35 mm
Max. conductor cross section flexible (fine-strand)25mm²
Max. conductor cross section solid (solid, stranded)1.5mm²
Signalling at the deviceOptic
With remote signalling contactYes
Nominal discharge surge current (8/20)15kA
Degree of protection (IP)IP20