Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Version as main switchYes
Number of auxiliary contacts as normally open contact0
Conditioned rated short-circuit current Iq-kA
Number of auxiliary contacts as change-over contact0
Version as safety switchYes
Rated operating voltage400 - 415V
Rated operation power at AC-3, 400 V-kW
Degree of protection (IP), front sideIP65
Version as emergency stop installationYes
Type of control elementDoor coupling rotary drive
Suitable for front mounting 4-holeYes
Rated short-time withstand current lcw13kA
Colour control elementBlack
Rated operation power at AC-23, 400 V220kW
Version as maintenance-/service switchYes
Suitable for floor mountingYes
Voltage release optionalNo
Suitable for distribution board installationNo
Rated permanent current at AC-21, 400 V400A
Version as reversing switchNo
Suitable for intermediate mountingNo
Suitable for front mounting centreNo
Switching power at 400 V220kW
Device constructionComplete device in housing
Rated permanent current at AC-23, 400 V400A
Rated permanent current Iu400A
Max. rated operation voltage Ue AC1000V