Aleta.hr
Main Product Image

2CCS861002R0204 | S801S-C20-R HIGH PERFORMANCE MCB

Code: 1858362

ManufacturerABB
Catalog number2CCS861002R0204
EAN code7612271209902

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Voltage typeAC/DC
Rated voltage400V
Frequency50 - 60Hz
Rated current20A
Built-in depth82.5mm
Over voltage category3
Degree of protection (IP)IP20
Rated insulation voltage Ui690V
Current limiting class3
Explosion-proofNo
Width in number of modular spacings1
Release characteristicC
Power loss3.5W
Pollution degree3
Concurrently switching neutral conductorNo
Number of protected poles1
Connectable conductor cross section solid-core0 - 50mm²
Suitable for flush-mounted installationNo
Additional equipment possibleYes
Ambient temperature during operating-25 - 60°C
Connectable conductor cross section multi-wired0 - 70mm²
Flush-mounted installationNo
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V50kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V25kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V25kA
Number of poles (total)1
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V50kA
Rated impulse withstand voltage Uimp8kV
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCS861002R0204 | S801S-C20-R HIGH PERFORMANCE MCB

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Voltage type

AC/DC

Rated voltage

400V

Frequency

50 .. 60Hz

Rated current

20A

Built-in depth

82.5mm

Over voltage category

3

Degree of protection (IP)

IP20

Rated insulation voltage Ui

690V

Current limiting class

3

Explosion-proof

Width in number of modular spacings

1

Release characteristic

C

Power loss

3.5W

Pollution degree

3

Concurrently switching neutral conductor

Number of protected poles

1

Connectable conductor cross section solid-core

0 .. 50mm²

Suitable for flush-mounted installation

Additional equipment possible

Ambient temperature during operating

-25 .. 60°C

Connectable conductor cross section multi-wired

0 .. 70mm²

Flush-mounted installation

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

50kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

25kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

25kA

Number of poles (total)

1

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

50kA

Rated impulse withstand voltage Uimp

8kV

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.