

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
2 - 18A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
64 - 160A
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
With switched-off indicator
No
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
2 - 10A
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
With integrated under voltage release
No
Degree of protection (IP)
IP20
Number of poles
4
From same serie
NZMH2-4-VX160-T

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
2 .. 18A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
64 .. 160A
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
With switched-off indicator
Rated permanent current Iu
160A
Adjustment range short-term delayed short-circuit release
2 .. 10A
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Complete device with protection unit
Motor drive integrated
With integrated under voltage release
Degree of protection (IP)
IP20
Number of poles
4
From same serie
We use cookies to enhance your experience.