Technical specifications
Construction size2 modular spacing
Mounting methodDIN rail (top hat rail) 35 mm
Remote signallingNo
Test classType 1 + 2
Max. continuous voltage DC0V
Voltage protection level N-PE1.4kV
Follow current extinguishing capability0kA
Max. continuous voltage AC260V
Max. PV-voltage0V
Integrated backup fuseNo
Signalling at the deviceOptic
Voltage protection level L-N1.5kV
Nominal voltage DC0V
Max. conductor cross section solid (solid, stranded)25mm²
Voltage protection level (DC+ - DC-)0kV
Max. conductor cross section flexible (fine-strand)35mm²
System configuration TN-SYes
Voltage protection level (DC+/DC- - PE)0kV
System configuration TTYes
System configuration otherYes
Energy-coordinated protection effect with regard to the terminal equipmentNo
System configuration TN-CNo
System configuration DCNo
Specific energy (W/R)625kJ/Ohm
Max. overcurrent protection device, parallel connection (fuse)0A
Voltage switching spark gap technologyYes
System configuration TNYes
Voltage protection level L-PE1.5kV
System configuration TN-C-SNo
System configuration ITNo
Overcurrent protected voltage tappingNo
Max. overcurrent protection device, series connection (fuse)0A
Lightning impulse current (10/350 µs)12.5kA
Number of poles2
Voltage protection level1.5kV
Nominal voltage AC240V
Degree of protection (IP)IP20