Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
DIN rail (top hat rail) mounting optional
Yes
Rated permanent current Iu
400A
Motor drive integrated
No
Complete device with protection unit
Yes
Overload release current setting
224.0 - 320A
With switched-off indicator
No
Adjustment range undelayed short-circuit release
1600 - 3200A
With integrated under voltage release
No
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Type of control element
Toggle
Integrated earth fault protection
No
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated voltage
220 - 690V
1SDA100518R1 | XT5H 400 TMA 320-3200 4p F F InN=50%In

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
400A
Motor drive integrated
Complete device with protection unit
Overload release current setting
224.0 .. 320A
With switched-off indicator
Adjustment range undelayed short-circuit release
1600 .. 3200A
With integrated under voltage release
Motor drive optional
Position of connection for main current circuit
Front side
Type of control element
Toggle
Integrated earth fault protection
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Rated voltage
220 .. 690V