- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
800A
Type of control element
Toggle
Overload release current setting
320.0 - 800A
Degree of protection (IP)
IP20
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
No
With switched-off indicator
No
Rated voltage
220 - 690V
Position of connection for main current circuit
Front side
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
From same serie
1SDA100854R1 | XT7S 800 Ekip Hi-Touch LSI In800A 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
800A
Type of control element
Toggle
Overload release current setting
320.0 .. 800A
Degree of protection (IP)
IP20
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Motor drive optional
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
With switched-off indicator
Rated voltage
220 .. 690V
Position of connection for main current circuit
Front side
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Complete device with protection unit
Motor drive integrated
From same serie