Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
220 - 690V
DIN rail (top hat rail) mounting optional
Yes
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
No
Type of control element
Toggle
Motor drive optional
Yes
With switched-off indicator
No
Overload release current setting
640.0 - 1600A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Motor drive integrated
No
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Position of connection for main current circuit
Front side
Adjustment range undelayed short-circuit release
1600 - 16000A
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
From same serie
1SDA100873R1 | XT7S 1600 Ekip G Dip LS/I In1600A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
220 .. 690V
DIN rail (top hat rail) mounting optional
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
Type of control element
Toggle
Motor drive optional
With switched-off indicator
Overload release current setting
640.0 .. 1600A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Motor drive integrated
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Position of connection for main current circuit
Front side
Adjustment range undelayed short-circuit release
1600 .. 16000A
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release