Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Integrated earth fault protection
Yes
Overload release current setting
320.0 - 800A
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Rated permanent current Iu
800A
DIN rail (top hat rail) mounting optional
Yes
Rated voltage
220 - 690V
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
With integrated under voltage release
No
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
Motor drive integrated
No
Motor drive optional
Yes
Complete device with protection unit
Yes
From same serie
1SDA100914R1 | XT7H 800 Ekip Touch Meas.LSIG In800 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Integrated earth fault protection
Overload release current setting
320.0 .. 800A
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Rated permanent current Iu
800A
DIN rail (top hat rail) mounting optional
Rated voltage
220 .. 690V
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
With integrated under voltage release
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
Motor drive integrated
Motor drive optional
Complete device with protection unit
From same serie