Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
With integrated under voltage release
No
With switched-off indicator
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Degree of protection (IP)
IP20
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Overload release current setting
320.0 - 800A
Rated voltage
220 - 690V
Number of poles
3
Device construction
Built-in device fixed built-in technique
Motor drive integrated
No
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Motor drive optional
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
From same serie
1SDA100938R1 | XT7H 800 Ekip G Touch LSIG In800A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With integrated under voltage release
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Type of control element
Toggle
Degree of protection (IP)
IP20
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Overload release current setting
320.0 .. 800A
Rated voltage
220 .. 690V
Number of poles
3
Device construction
Built-in device fixed built-in technique
Motor drive integrated
Position of connection for main current circuit
Front side
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Motor drive optional
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
From same serie