

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 - 690V
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1000 - 10000A
Overload release current setting
400.0 - 1000A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
Number of poles
3
With switched-off indicator
No
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Type of control element
Toggle
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP20
From same serie
1SDA100963R1 | XT7L 1000 Ekip Dip LSIG In=1000A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1000 .. 10000A
Overload release current setting
400.0 .. 1000A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
Number of poles
3
With switched-off indicator
Position of connection for main current circuit
Front side
Complete device with protection unit
Type of control element
Toggle
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP20
From same serie
We use cookies to enhance your experience.