Aleta.hr
Main Product Image

1SDA100974R1 | XT7L 800 Ekip Touch Meas.LSI In800 3p FF

Code: 1893819

ManufacturerABB
Catalog number1SDA100974R1
EAN code8056221010283

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu800A
Rated voltage220 - 690V
Overload release current setting320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalYes
With switched-off indicatorNo
With integrated under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Complete device with protection unitYes
Number of poles3
Motor drive integratedNo
Degree of protection (IP)IP20
Motor drive optionalYes
Type of control elementToggle
Position of connection for main current circuitFront side
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA100974R1 | XT7L 800 Ekip Touch Meas.LSI In800 3p FF

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Rated voltage

220 .. 690V

Overload release current setting

320.0 .. 800A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

With switched-off indicator

With integrated under voltage release

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Complete device with protection unit

Number of poles

3

Motor drive integrated

Degree of protection (IP)

IP20

Motor drive optional

Type of control element

Toggle

Position of connection for main current circuit

Front side

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.