Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
With switched-off indicator
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
Yes
Overload release current setting
640.0 - 1600A
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
No
Number of poles
3
Rated voltage
220 - 690V
Type of control element
Toggle
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
Motor drive integrated
No
From same serie
1SDA100977R1 | XT7L 1600 Ekip Touch Meas.LSI 1600 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
With switched-off indicator
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
Overload release current setting
640.0 .. 1600A
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
Number of poles
3
Rated voltage
220 .. 690V
Type of control element
Toggle
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
Motor drive optional
Degree of protection (IP)
IP20
Motor drive integrated
From same serie