Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
320.0 - 800A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Rated voltage
220 - 690V
DIN rail (top hat rail) mounting optional
Yes
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of poles
3
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Motor drive optional
Yes
Complete device with protection unit
Yes
With switched-off indicator
No
Degree of protection (IP)
IP20
Motor drive integrated
No
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally open contact
0
1SDA100982R1 | XT7L 800 Ekip Hi-Touch LSI In800A 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
320.0 .. 800A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Rated voltage
220 .. 690V
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Front side
Device construction
Built-in device fixed built-in technique
Number of poles
3
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Motor drive optional
Complete device with protection unit
With switched-off indicator
Degree of protection (IP)
IP20
Motor drive integrated
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally open contact
0