Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
No
Rated permanent current Iu
1600A
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
220 - 690V
Number of poles
3
Overload release current setting
640.0 - 1600A
DIN rail (top hat rail) mounting optional
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
No
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Position of connection for main current circuit
Front side
Type of control element
Toggle
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive integrated
No
Motor drive optional
Yes
From same serie
1SDA100985R1 | XT7L 1600 Ekip Hi-Touch LSI 1600A 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
Rated permanent current Iu
1600A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Rated voltage
220 .. 690V
Number of poles
3
Overload release current setting
640.0 .. 1600A
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Position of connection for main current circuit
Front side
Type of control element
Toggle
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive integrated
Motor drive optional
From same serie