Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated permanent current Iu
1600A
Integrated earth fault protection
Yes
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
With switched-off indicator
No
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Type of control element
Toggle
With integrated under voltage release
No
Motor drive optional
Yes
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
From same serie
1SDA100989R1 | XT7L 1600 Ekip Hi-Touch LSIG 1600A 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated permanent current Iu
1600A
Integrated earth fault protection
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
0
Complete device with protection unit
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Type of control element
Toggle
With integrated under voltage release
Motor drive optional
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
From same serie