Aleta.hr
Main Product Image

1SDA101004R1 | XT7L 1250 Ekip G Touch LSIG In1250 3p FF

Code: 1893849

ManufacturerABB
Catalog number1SDA101004R1
EAN code8056221010580

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Device constructionBuilt-in device fixed built-in technique
Overload release current setting500.0 - 1250A
Type of electrical connection of main circuitBolt connection
Rated permanent current Iu1250A
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally closed contact0
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Number of auxiliary contacts as normally open contact0
Adjustment range undelayed short-circuit release1875.0 - 18750A
DIN rail (top hat rail) mounting optionalYes
With switched-off indicatorNo
Motor drive integratedNo
Type of control elementToggle
Number of auxiliary contacts as change-over contact0
With integrated under voltage releaseNo
Position of connection for main current circuitFront side
Motor drive optionalYes
Number of poles3
Degree of protection (IP)IP20
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101004R1 | XT7L 1250 Ekip G Touch LSIG In1250 3p FF

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

220 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Device construction

Built-in device fixed built-in technique

Overload release current setting

500.0 .. 1250A

Type of electrical connection of main circuit

Bolt connection

Rated permanent current Iu

1250A

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Number of auxiliary contacts as normally open contact

0

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

DIN rail (top hat rail) mounting optional

With switched-off indicator

Motor drive integrated

Type of control element

Toggle

Number of auxiliary contacts as change-over contact

0

With integrated under voltage release

Position of connection for main current circuit

Front side

Motor drive optional

Number of poles

3

Degree of protection (IP)

IP20

Complete device with protection unit

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.