Aleta.hr
Main Product Image

1SDA101116R1 | XT7S 1250 Ekip Dip LS/I In=1250A 4p F F

Code: 1893951

ManufacturerABB
Catalog number1SDA101116R1
EAN code8056221014199

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Rated voltage220 - 690V
Rated permanent current Iu1250A
Adjustment range short-term delayed short-circuit release1250 - 12500A
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1250 - 12500A
DIN rail (top hat rail) mounting optionalYes
With integrated under voltage releaseNo
Overload release current setting500.0 - 1250A
Number of poles4
Type of control elementToggle
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Integrated earth fault protectionNo
With switched-off indicatorNo
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Complete device with protection unitYes
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101116R1 | XT7S 1250 Ekip Dip LS/I In=1250A 4p F F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Rated voltage

220 .. 690V

Rated permanent current Iu

1250A

Adjustment range short-term delayed short-circuit release

1250 .. 12500A

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1250 .. 12500A

DIN rail (top hat rail) mounting optional

With integrated under voltage release

Overload release current setting

500.0 .. 1250A

Number of poles

4

Type of control element

Toggle

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Integrated earth fault protection

With switched-off indicator

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Motor drive optional

Complete device with protection unit

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP20

Motor drive integrated

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.