Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting400 - 1000A
With integrated under voltage releaseNo
Degree of protection (IP)IP20
Type of electrical connection of main circuitBolt connection
Type of control elementToggle
Number of auxiliary contacts as change-over contact0
Motor drive integratedNo
With switched-off indicatorNo
Position of connection for main current circuitFront side
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1000 - 10000A
Adjustment range short-term delayed short-circuit release1000 - 10000A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionYes
Complete device with protection unitYes
Rated permanent current Iu1000A
Number of poles4
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA