Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 - 690V
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
320.0 - 800A
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Position of connection for main current circuit
Front side
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive integrated
No
With integrated under voltage release
No
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
From same serie
1SDA101126R1 | XT7S 800 Ekip Touch LSI In=800A 4p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Rated permanent current Iu
800A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
320.0 .. 800A
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Position of connection for main current circuit
Front side
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive integrated
With integrated under voltage release
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
From same serie