

Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA101177R1 | XT7H 1600 Ekip Dip LSI In=1600A 4p F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
1600 .. 16000A
Overload release current setting
640.0 .. 1600A
Position of connection for main current circuit
Front side
With integrated under voltage release
Motor drive optional
With switched-off indicator
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Rated permanent current Iu
1600A
Number of poles
4
Rated voltage
220 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA