Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1600 - 16000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Yes
With integrated under voltage release
No
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Number of poles
4
Rated voltage
220 - 690V
Type of control element
Toggle
Motor drive integrated
No
Degree of protection (IP)
IP20
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
From same serie
1SDA101181R1 | XT7H 1600 Ekip Dip LSIG In=1600A 4p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1600 .. 16000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of poles
4
Rated voltage
220 .. 690V
Type of control element
Toggle
Motor drive integrated
Degree of protection (IP)
IP20
Motor drive optional
Position of connection for main current circuit
Front side
Complete device with protection unit
From same serie