Technical specifications

Rated permanent current Iu800A
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of poles4
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Overload release current setting320.0 - 800A
Rated voltage220 - 690V
Type of control elementToggle
Number of auxiliary contacts as change-over contact0
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
With switched-off indicatorNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Position of connection for main current circuitFront side
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
Integrated earth fault protectionNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Adjustment range undelayed short-circuit release1200.0 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101198R1 | XT7H 800 Ekip Hi-Touch LSI In800A 4p FF

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

With integrated under voltage release

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP20

Overload release current setting

320.0 .. 800A

Rated voltage

220 .. 690V

Type of control element

Toggle

Number of auxiliary contacts as change-over contact

0

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Position of connection for main current circuit

Front side

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

Integrated earth fault protection

Motor drive optional

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Suitable for DIN rail (top hat rail) mounting