Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA101225R1 | XT7H 1600 Ekip Dip LIG In=1600A 4p F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
1600 .. 16000A
Rated voltage
220 .. 690V
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Position of connection for main current circuit
Front side
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Complete device with protection unit
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
640.0 .. 1600A
Motor drive integrated
Type of control element
Toggle
Number of poles
4
Motor drive optional
Degree of protection (IP)
IP20