Aleta.hr
Main Product Image

1SDA101237R1 | XT7L 1600 Ekip Dip LSIG In=1600A 4p F F

Code: 1894064

ManufacturerABB
Catalog number1SDA101237R1
EAN code8056221015400

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting640.0 - 1600A
With switched-off indicatorNo
Rated permanent current Iu1600A
With integrated under voltage releaseNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Rated voltage220 - 690V
Adjustment range short-term delayed short-circuit release1600 - 16000A
Adjustment range undelayed short-circuit release1600 - 16000A
Motor drive integratedNo
Number of auxiliary contacts as normally open contact0
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Position of connection for main current circuitFront side
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
Type of electrical connection of main circuitBolt connection
Degree of protection (IP)IP20
Number of auxiliary contacts as change-over contact0
Number of poles4
Type of control elementToggle
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101237R1 | XT7L 1600 Ekip Dip LSIG In=1600A 4p F F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

640.0 .. 1600A

With switched-off indicator

Rated permanent current Iu

1600A

With integrated under voltage release

Motor drive optional

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Rated voltage

220 .. 690V

Adjustment range short-term delayed short-circuit release

1600 .. 16000A

Adjustment range undelayed short-circuit release

1600 .. 16000A

Motor drive integrated

Number of auxiliary contacts as normally open contact

0

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Position of connection for main current circuit

Front side

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

Type of electrical connection of main circuit

Bolt connection

Degree of protection (IP)

IP20

Number of auxiliary contacts as change-over contact

0

Number of poles

4

Type of control element

Toggle

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.