Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
DIN rail (top hat rail) mounting optional
Yes
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
220 - 690V
Integrated earth fault protection
No
Overload release current setting
640.0 - 1600A
Type of control element
Toggle
Rated permanent current Iu
1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Degree of protection (IP)
IP20
With switched-off indicator
No
Complete device with protection unit
Yes
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
0
From same serie
1SDA101249R1 | XT7L 1600 Ekip Touch Meas.LSI 1600 4p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Rated voltage
220 .. 690V
Integrated earth fault protection
Overload release current setting
640.0 .. 1600A
Type of control element
Toggle
Rated permanent current Iu
1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Number of poles
4
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Degree of protection (IP)
IP20
With switched-off indicator
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Number of auxiliary contacts as change-over contact
0
From same serie